Lucent Technologies 3000 VA Power Supply User Manual


 
UPS Operation4
Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)
44
5 Press and hold the Output On button until the alarm beeps again.
Two indicators, corresponding with the current setting, remain flashing.
The output voltage is factoryĆconfigured for 230V.
OVERLOAD
I1
I2
I3
OUTPUT ON
220V230V240V 208V
Figure 19. Output Voltage Indicators
6 Press the Output Off button to scroll through the output voltage
options, top to bottom. Each time you press the button, the UPS beeps and
the next two indicators flash.
NOTE If you do not save a selection within two minutes, the setup automatically aborts
and switches back to the original configuration.
7 Press and hold the Output On button until the alarm beeps to select and
save the output voltage. Failure to release the button immediately after the
beep will cause the UPS to abort the setup.
8 Press and hold the Output On button until you hear the UPS beep
(approximately one second).
The
Indicator remains lit and the Output On Indicator turns on,
indicating the UPS is online.
9 Turn the Bypass switch on the Bypass Module to the NORMAL position.
The front panel displays the percentage of full load being applied to the
UPS. The UPS is now in Normal Mode with the load online.