MGE UPS Systems 1000 RT2U Power Supply User Manual


 
Output personalization
(1) These parameters may be modified only when the UPS is OFF. Detailed comments are available in the Personal
Solution-Pac software.
ON/OFF personalization
Battery personalization
4.4 Personalization using external software
Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings". Note that the Linux/Unix/MacOS versions of the
Personal Solution-Pac software do not offer this possibility.
Function Factory Setting
Other available
settings
Comments
Battery test Weekly test
No test / daily test /
monthly test
Low-battery warning 20% 0 to 100% Adjustable in 1% steps.
Selection of the
backup time
Automatic detection
of number of battery
modules
13 to 200 Ah
Battery protection
against excessive
discharges
Enabled Disabled
Excessive discharges when function
disabled, MGE Office Protection Systems
warranty no longer applies.
Function Factory Setting
Other available
settings
Comments
Start on battery power Enabled Disabled
Automatic restart Enabled Disabled
The UPS restarts automatically when AC
power returns.
Energy savings Disabled Enabled
When function enabled, battery shuts down
when power drops to <5%.
Detection of phase/
neutral inversion
(SWF)
Enabled Disabled
Neutral inversion (SWF) When function
enabled, the UPS remains OFF if the
system detects phase/neutral inversion.
Function Factory Setting
Other available
settings
Comments
Output voltage
(1)
120 Volts AC 100 to 127 Volts AC
Frequency
converter
(1)
Disabled Enabled
The connected devices are never trans-
ferred to the bypass.
Output frequency
(1)
Automatic selection 50 or 60 Hz
User selectable only if the frequency-
converter function is enabled.
Transfer to the
bypass AC input
(1)
Bypass AC power
must be within
tolerances
Bypass AC power
may be outside
tolerances
Overload level
(1)
100% 30 / 50 / 70% Alarm if threshold is overrun.
Pulsar
Access to Maintenance and Personalization Data
4 — 2
86-86700-00 A01