MGE UPS Systems 1000 RT2U Power Supply User Manual


 
Appendix
Technical Specifications
(1) EXB Module for Pulsar 1000 and Pulsar 1500
(2) EXB RT2U Module for Pulsar 1000 RT2U and Pulsar 1500 RT2U.
(3) 900W, in standard configuration, 800W with at least 1 EXB connected
(4) 1290W in standard configuration, 1200W with at least 1 EXB connected
(5) Values for 33% / 66% / 100% of nominal power rating
(6) Adjustable from 100V to 127V using the UPS Config software
(7) Frequency-converter mode is programmable using the UPS Config software
(8) Nominal, for 120V output voltage
Pulsar 700
Pulsar 1000
Pulsar 1000 RT2U
Pulsar 1500
Pulsar 1500 RT2U
Pulsar EXB
1000/1500 (1)
Pulsar EXB
1000/1500 RT2U (2)
Output power 700VA / 630W 1000VA /900 W
(3)
1500VA /1290 W
(4)
AC input power
Voltage
Frequency
Power factor
Single phase 60 / 70 / 80V to 142V (5)
50/60 Hz autoselect
> 0.95
Load output
Voltage
Frequency
Harmonic distortion
Overload capacity
Current
Single phase 120V ±3% (6)
50/60 Hz ±0.5% (7)
< 4% for linear load, < 6% for nonlinear load
102% continuous, 130% 12s, > 130% 2s
5.8A
(8)
8.3A
(8)
12.5A
(8)
Battery, sealed lead acid,
maintenance free
2x12V – 7Ah 3x12V – 7Ah 3x12V – 9Ah
Two string of
3x12V -9Ah
Environment
Operating temperature range
Relative humidity
Leakage current
Storage temperature range
Altitude
0°C to 40°C
20% to 90% (without condensation)
< 1.1mA
-25°C to 40°C
1000 m
Standards and certification
Safety
EMC
Surge suppressor
UL 1778 (4th edition), CSA C22.2 No 107.3-05
FCC Subpart B, class A
IEEE/ANSI 62.41
Appendix
A — 1
86-86700-00 A01
ENGLISH