MGE UPS Systems 40-150kVA Power Supply User Manual


 
Installation and User Manual
NOTE The cooling fans will remain operational when the UPS is placed on
Maintenance Bypass mode to prevent the optional input/output transformers
inside the UPS from overheating. If it is necessary to de-energize the fans,
move the fan control switch (SR2) to the “OFF” position.
CAUTION In this mode of operation, the UPS is ready for maintenance, but voltage is
still present on terminal blocks and various internal components.
Now the UPS is ready for maintenance.
3.8.2 From Maintenance Bypass to Normal Mode
WARNING Failure to follow the proper Startup sequence will result in load loss. After
SR1 is set to “TRANSFER,” it takes the UPS five (5) to six (6) \seconds to test
the input power before turning on the “Static Switch”. During this time, the
load is still supplied by the Maintenance Bypass line, and moving SR1 to
“NORMAL” will result in interruption of power to the load.
1. Move the fan control switch (SR2) to the “ON” position if the cooling fans were de-energized during
maintenance.
2. Turn the manual bypass switch SR1 to the "TRANSFER" position.
3. Wait for the GUI display to go on (at least 5 seconds).
4. Turn the Inverter off by pressing the gray "Inverter OFF" pushbutton on the front panel for approximately
3 seconds if your Comet has been programmed to automatically restart.
CAUTION ALWAYS turn the Inverter off before rotating the Manual Bypass Switch (SR1).
5. Close the battery disconnect circuit breaker(s) QF1.
6. Turn the manual bypass switch SR1 to the "NORMAL" position.
7. Turn the Inverter on by pressing the green “Inverter ON" pushbutton on the front panel. If the transfer
conditions are not satisfied (bypass out of tolerance or other reason), a forced transfer will be required.
Refer to the "Forced Transfers" section for more information.
Now the UPS is in normal operating mode. The green "Load Protected" LED is illuminated on the front panel,
and the operating status of the UPS is provided by the GUI display.
Operation 3 —986-160310-00 E00