Installation and User Manual
iii86-160310-00 E00 Certification Standards and Safety of Persons
WARNING HIGH LEAKAGE CURRENT. Earth connection essential before connecting
supply.
ATTENTION COURANT DE FUITE ELEVE. Raccordement a la terre indispensable avant le
raccordement au reseau.
WARNUNG! Hoher Ableitstrom Vor Inbetriebnahme Schutzleiterverbindung herstellen.
Certification Standards - Three Phase UPS
◗ IEC 1004/ANSI C62.41 Standards for Surge Withstand Ability.
◗ FCC Part 15, Subpart J, Class A.
◗ UL/cUL 1778, Standard for Uninterruptible Power Supply Equipment.
◗ NEMA PE 1 - Uninterruptible Power Systems.
◗ NFPA 70 - National Electrical Code.
◗ ISO 9001.
Safety of Persons
◗ The UPS has its own internal power source (the battery). Consequently, the power outlets may be
energized even if the UPS is disconnected from the AC power source.
◗ The UPS must be properly grounded.
◗ The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the
directives listed below must be observed:
- Never burn the battery (risk of explosion).
- Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
- Comply with all applicable regulations for the disposal of the battery.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal
objects, use tools with insulated handles.
- Do not lay tools or metal parts on top of batteries.
Product Safety
◗ A protection circuit breaker must be installed upstream and be easily accessible.
◗ The UPS can be disconnected from the AC power source by opening the input circuit breaker.
◗ UPS must be connected to a nearby power source that is easily accessible.
◗ Never block the ventilation grates of the UPS.
◗ The UPS must be installed in a controlled environment.
Special Precautions
◗ The UPS connection instructions and operation described in the manual must be followed in the indicated
order.
◗ Check that the indications on the rating plate correspond to your AC powered system and to the actual
electrical consumption of all the equipment to be connected to the UPS.
◗ Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be
energized for a period of 24 hours, at least once every 3 months (for a normal storage temperature less
than 25°C). This charges the battery, thus avoiding possible irreversible damage.