2.2.2 Electrical Specifications
Table 2-1: Electrical Specifications for the Galaxy 4000.
NOTE: Interrupted Transfer to Bypass Source:
If the bypass source is beyond the conditions stated below, the UPS will make an interrupted transfer (not more than 100 msec. in duration).
1. Bypass voltage greater than +15%, -15% from the UPS rated output voltage.
2. Bypass frequency greater than ±2 Hz from the UPS rated output frequency.
2.3 Electrical Connections
CAUTION Only an authorized electrical professional should access electrical connections.
A severe shock hazard exists.
The ONLY user serviceable items in the Galaxy 4000 unit are:
A. The main and bypass power connections.
B. The load connection.
C. Any cable connection to external or auxiliary modules.
D. The communication card options.
The access method for connections made to the communication cards is clearly seen when the front right door to
the Galaxy 4000 unit is opened. However, access to the main, bypass and load connections is made through the
removal of the safety panel located in the lower right of the Galaxy 4000 (with the right door open). This safety panel
is removed by first removing the screws securing the panel. It can then be removed by lifting the safety panel away
from the unit.
CAUTION Before making any electrical connections, verify that all battery disconnect circuit
breakers (CB1) are in the "off" position. Customer-supplied upstream protective
devices and distribution circuits should be OFF.
Output Power Rating (0.8) PF
40KVA 50KVA 65KVA 75KVA
UPS Voltage (input/output) 208/208 208/208 208/208 208/208
Input/Output Requirements & Frequency Three phase, Three wire + N + G, 60Hz
Input Phase Rotation A,B,C Clockwise
Input Power Factor >.98
Input Current 102A 127A 166A 191A
Maximum Input Current(at low line -15%) 120A 150A 195A 225A
Bypass Current 111A 139A 180A 208A
Output Current 111A 139A 180A 208A
Battery Voltage
198 VDC End Voltage 240VDC Nominal 282VDC Max. Maintenance Voltage
Max. Battery Current at Nominal Battery Voltage (240 VDC at 100% Load) 157A 196A 255A 294A
Max. Battery Current at Nominal End- Voltage (198 VDC at 100% Load) 190A 238A 309A 357A
Battery Disconnect Circuit Breaker Rating 250A 400A
Input, Bypass, and Maintenance Bypass (optional) Switch Rating 150A 250A
Input Fuse Rating 200A 300A
Output Isolation Circuit Breaker Rating 175A 300A
Galaxy 4000
Installation2 — 2 86-173010-00 A00