MGE UPS Systems AmpMeter PDU Power Supply User Manual


 
3. Operations
Command Line Interface
Logging In
Logging in through Telnet requires directing the Telnet client to the configured IP address of the unit.
Logging in through the Console (RS232) port requires the use of a terminal or terminal emulation software
configured to support ANSI or VT100 and a supported data rate (300, 1200, 2400, 4800, 9600, 19200, 38400,
57600, or 115200 BPS) - 8 data bits-no parity-one stop bit and Device Ready output signal (DTR or DSR).
To log in by RS-232 or Telnet:
1. Press Enter. The following appears, where x.xx is the firmware version:
AmpMeter PDU Version x.xx
Username:
NOTE: Logging in by Telnet will automatically open a session. It is not necessary to press Enter.
2. At the Username: and Password: prompts, enter a valid username and password. And press Enter.
You are given three attempts to enter a valid username and password combination. If all three fail, the
session ends.
When you enter a valid username and password, the command prompt (AmpMeter PDU:) appears. If a location
identifier was defined, it will be displayed before the AmpMeter PDU: prompt. See Creating a location
description on page 26 for more information.
You may enter commands in any combination of uppercase and lowercase. You must enter all command
characters correctly; there are no command abbreviations. There are two types of commands: operations and
administration. A user must have administrative privileges to use the administration commands. The following
tables list and briefly describe each command.
Operations Command Summary
Command Description
ILoad Displays the cumulative input load per branch or phase
Istat Displays the status of the infeeds
Connect Connects to a serial port
Login Ends the current session and brings up the Username: prompt
Logout Ends a session
Quit Ends a session
List Ports Lists all accessible serial ports for the current user
Administrative Command Summary
Add Porttouser Grants a user access to one or all serial ports
Create User Adds a user account
Delete Portfromuser Removes access to one or all serial ports
List User Displays all accessible outlets/groups/ports for a user
List Users Displays privilege levels for all users
Remove User Deletes a user account
Restart Performs a warm boot
Set Envmon Name Specifies a descriptive field for the integrated Environmental Monitor
Set Envmon THS Name Specifies a descriptive field for a temperature-humidity sensor
Page 18 - 301-0399-3 Rev B.