MGE UPS Systems AmpMeter PDU Power Supply User Manual


 
2. Installation
Mounting
Figure 3. Mounting
Horizontal/Rack
Select the appropriate bracket mounting points
for proper mounting depth within the rack.
Attach the brackets to these mounting points
with two screws for each bracket.
Install the enclosure into your rack, using the
slots in each bracket. The slots allow about ¼
inch of horizontal adaptability to align with the
mounting holes of your rack.
Vertical/Tower
1.
2.
3.
1. Attach the removable flanges to the mount
points on the rear of the enclosure using M4
screws.
2. Attach the mounting L-brackets to the flanges
with the supplied screws, washers and nut
plates. The slots allow about 1½ inches of
vertical adaptability.
3. Attach the top and bottom brackets to your rack.
Connecting to the Power Source
To attach a power cord to the unit:
1. Plug the female end of the power cord firmly into its connector at the base.
2. Use a screwdriver to tighten the two screws on the retention bracket.
To connect to the power source:
Plug the male end of the power cord into the AC power source.