MGE UPS Systems EX 5RT Power Supply User Manual


 
4.5 Hot Swapping the Battery Module
Figure 4-3: Rear view of the battery module.
EX 5/7/11 RT System
Maintenance4 — 6 86-86000-00 A01
4.5.1 Disconnecting the Battery Module
1. Switch the battery circuit breaker(s) to the
OFF position.
2. Disconnect the cables and from the
power module.
The battery module can be replaced.
The connected equipment is powered by the UPS,
but not protected.
It is also possible to replace battery pack instead of
battery module.
Contact your nearest after sales support service.
CAUTION: Always replace both battery
packs with new ones.
To remove battery pack:
1. First, switch the battery circuit breaker(s) to the
OFF position.
See section 2.5 and follow instructions for battery
pack replacement.
4.5.2 Re-connecting the Battery Module
1. Reconnect the battery cables and to
the power module.
2. Switch the battery circuit breaker(s) to the
ON position.
14
4240
4240
14
42
40
14
Battery Module Power Module