2. Installation and connection
• Procedure for connection
to power supply output receptacle (IEC60320
C13)
2-3-2 Connecting a device to the power supply output (BU3002SW)
(1) Connect devices that require backup to the unit's power supply output receptacle or output terminal block.
Make sure that the total capacity of the devices connected to the output receptacle does not
exceed the output rated capacity of the BU3002SW. If the overload indication (
) is dis-
played, reduce the number of connected devices.
BU3002SW (Rated value of output capacity: Max. 3kVA/2100W)
“Power supply output” group Output receptacle Output terminal block
Group A C19: 1 (Rated capacity: 20A) 1 line (Rated capacity: 20A)
C13: 1 (Rated capacity: 15A)
Group B C13: 2 (Rated capacity: 15A) 1 line (Rated capacity: 20A)
Group C C13: 2 (Rated capacity: 15A)
Group B
Group B
Group A
Group C
Group A
• Procedure for connection
to power supply output receptacle (IEC60320
C19)
Connect it directly.
Connect it directly.
Plug of connected device
Plug of connected device
Group control of power supply output
See Page 24