54
6. Maintenance and inspection
Perform replacement on a stable and flat place.
Handle the battery carefully so that you do not drop it.
Not doing so could cause injury or burns due to liquid (acid) leakage.
Use a specified battery for replacement.
Not doing so may cause a fire.
Product model: BP100XS (Replacement battery pack for BU1002SW)
BP150XS: Two required (Replacement battery pack for BU3002SW)
Do not replace the battery in a place where there is flammable gas.
Spark may occur when connecting the battery, which may cause an explosion or fire.
If fluid (dilute sulfuric acid) leaks from the battery, do not touch the fluid.
Doing so may cause blindness or burns.
If it contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not disassemble or modify the battery.
Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.
Do not drop the battery and do not expose it to strong impact.
Dilute sulfuric acid may leak.
Do not short the battery with metal objects.
Doing so could cause an electric shock, fire or burn.
Some electrical energy still remains inside the spent battery.
6-2 Replacing the battery
The battery can be replaced while the unit is stopped (power supply output stopped).
* When replacing the battery, stop the connected devices, turn OFF the power switch of the UPS, and
disconnect the AC input plug from the wall.
* If an input power supply error such as a power failure occurs when replacing the battery while in opera-
tion, backup cannot be performed and output stops.
*Do not replace the battery during backup operation. Output will stop.
Caution
When the unit is used in compliance with UL standards or CE marking, do not replace the battery while in
operation (while power is being output). Replacing the battery while in operation does not comply with UL
standards or CE marking. Make sure to stop the operation of the unit before replacing the battery.
3. Guidelines for how often to check the battery (measure the backup time)
* The battery deteriorates even if it is stored. The higher the temperature is, the shorter the
life becomes.
Ambient temperature
20°C
30°C
Check once every 6 months
For the first 3 years after purchase
For the first 1.5 years after purchase
Check once a month
When 3 or more years have passed since purchase
When 1.5 or more years have passed since purchase
Caution (for battery replacement)