6. Contact Signal ratings
Signal output (BL, TR, BU, WB, BU) UPS Stop Signal input (BS)
Photo coupler ratings Input voltage HIGH(ON) 5 to 12 VDC
Appliable voltage: 35 VDC or less LOW(OFF) 0.7 VDC or less
Maximum current: 20 mA
Remote ON/OFF
Voltage between terminals: 5 VDC
Current when closed: max.10 mA
7. Contact Signal circuit inside the UPS
5. Remote ON/OFF connector
Front view
Screw size: Inch screw
#4-40 UNC
Pin assignment Pin number Signal name
1 Remote ON/OFF (+)
2 Remote ON/OFF (-)
8. Example of the use of the Contact Signal circuit
Example of BU signal output circuit and
the connected circuit
Example of BS signal input circuit and the
connected circuit
12V1K
TLP627
To port on P
C
BL
TR
BU
WB
BS
COM
2.4V 560
Remote ON/OFF (+)
Remote ON/OFF (-)
5V
10k
COM
UPS side
GND
BS
12V
1K
1.2K
TLP521
To port on PC