Introduction This section describes how to configure Concept & ProWORX32 to work the
TSXCUSBMBP.
Setting the
Optimum Baud
Rate in Concept
When using serial Modbus communications with Concept, a delay of approximately
50 milliseconds occurs before each Modbus request is transmitted.
When using Concept with the TSXCUSBMBP, a serial interface must be selected.
Therefore, the overall throughput of the TSXCUSBMBP with Concept is only slightly
above that of a serial Modbus interface. Setting the baud rate in Concept to 19200
instead of the 9600 default will slightly improve performance.
Setting the
Optimum Baud
Rate in
ProWORX32
When using serial Modbus communications with ProWORX32, there are no delays
inserted and the TSXCUSBMBP runs at the expected USB speed.