45
13. FDR service
M Download the IP addresses
• Connect the drive and the FDR server (PLC) to the Ethernet network.
• The server downloads the IP addresses to the Ethernet card.
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
You can also check, in the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu whether the [IP card] (IPC1)
(IPC2) (IPC3) (IPC4), [IP Mask] (IPM1) (IPM2) (IPM3) (IPM4) and [IP Gate] (IPG1) (IPG2) (IPG3) (IPG4)
parameters have values other than [0.0.0.0] (0) (0) (0) (0).
M Save the drive configuration parameters in the FDR server
• Configure the drive parameters.
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Specify that the drive configuration is to be downloaded from the FDR server on each power-up: [FDR Local Config.] (LCFG) = [No] (nO).
• Send a save command to the FDR server: [FDR Action] (FdrA)
= [SAVE] (SAUE).
After execution of the command, the [FDR Action] (FdrA) parameter reverts to the value [IDLE] (IdLE).
M Check that the system is operational
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
•The [FDR state] (FdrE) parameter should be at the value [OPE] (OPE).
If the save operation has not been successful, the card triggers a drive status [External fault com.] (EPF2).
b Replacing a drive
Procedure:
• Configure the drive.
• Turn off the drive.
• Connect the drive to the network.
• Check that the drive is operational.
M Configure the drive
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES).
• Specify that the drive configuration is to be downloaded from the FDR server on each power-up:
[FDR Local Config.] (LCFG) = [No] (nO).
These configurations are the default values.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu.
This menu can only be accessed in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
M Turn the drive off and then back on again
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken
into account.
M Connect the drive to the network
M Check that the system is operational
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
•The [FDR state] (FdrE) parameter should be at the value [OPE] (OPE).
If downloading has not been possible after a period of 2 min following assignment of the IP addresses, the card triggers a drive status
[External fault com.] (EPF2).