SonicWALL CDP 6080B Computer Drive User Manual


 
SonicWALL CDP 6080 / 6080B Getting Started Guide Page 39
Mounting the SonicWALL CDP 6080
The SonicWALL CDP appliance is designed to be mounted in a
standard 19-inch rack mount cabinet. The following conditions
are required for proper installation:
Use the mounting hardware recommended by the rack
manufacturer and ensure that the rack is adequate for the
application.
Four mounting screws, compatible with the rack design,
must be used and hand tightened to ensure secure
installation. Choose a mounting location where all four
mounting holes line up with those of the mounting bars of
the 19-inch, rack mount cabinet.
Mount in a location away from direct sunlight and sources
of heat. An ambient temperature of 104º F (40º C) is the
maximum allowed.
Route cables away from power lines, fluorescent lighting
fixtures, and sources of noise such as radios, transmitters,
and broadband amplifiers.
As shipped from the factory this SonicWALL product
includes two power supplies for redundant AC power and
added reliability. A field conversion is available to convert to
DC mains.
The included power cord is intended for use in North
America AC mains installation only. For European Union
(EU) customers, and DC mains, a power cord is not
included.
Ensure that no water or excessive moisture can enter the
unit.
Allow unrestricted airflow around the unit and through the
vents on the side of the unit. A minimum of 1 inch
(25.44mm) clearance is recommended.
If installed in a closed or multi-unit rack assembly, the
operating ambient temperature of the rack environment
may be greater than room ambient. Therefore,
consideration should be given to installing the equipment in
an environment compatible with the maximum
recommended ambient temperature shown above.
Mount the SonicWALL appliances evenly in the rack in
order to prevent a hazardous condition caused by uneven
mechanical loading.
Consideration must be given to the connection of the
equipment to the supply circuit. The effect of overloading
the circuits has minimal impact on overcurrent protection
and supply wiring. Appropriate consideration of equipment
nameplate ratings must be used when addressing this
concern.
DC configuration includes input cable with protective
earthing conductor (green and yellow wire). This conductor
must be connected to safety earth ground of circuit.
Never remove or install a power supply while the power
cord is attached to the power supply that is being removed
or installed.
A suitably rated and approved branch circuit breaker shall
be provided as part of the building installation. Follow local
code when purchasing materials or components.