Toshiba 1000 Power Supply User Manual


 
18
6. Computer and Alarm Connections
At the rear of the UPS is an interface that allows direct communication with a computer
system (see Figure 2, Pg. 14). There is a RS232 serial data interface, a USB data
interface, and an emergency power off switch. The RS232 port and the USB interface
cannot be used simultaneously.
In addition there is an optional interface slot that allows for the installation of
communications cards. It may be used in parallel with either the RS232 or USB ports.
An SNMP/WEB card is available for the optional interface slot that allows for the
RemotEye II to manage and monitor the system over a network or over the internet.
6.1 RS-232 Standard Interface Port
Only the communication cable provided with the UPS may be used to connect the UPS
to a computer when using the RS232 port of the UPS. Ensure that the operating system
of the computer supports RS232 communications. Other advanced power protection
solutions, such as SNMP, are available from your dealer.
The RS-232 interface uses a 9-pin D-sub connector. The names and functions of the port
pins are listed in the following table.
Pin #
Signal
Direction (re UPS)
Functions
2
TxD
Output
TxD Output
3
RxD
Input
RxD / Inverter Off Input
5
Common
Common
6
Output (Normally Open)
AC Fail (13VDC)
8
Output (Normally Open)
Low Battery (13VDC)
9
Output
8–24 VDC Power
Note: In Battery mode, the UPS will be turned off 2 minutes after 5V is applied to Pin 3 and Pin 5 for more
than 5seconds.
Table 1 : RS232 Pin Out Signal
DB9 Female Connector Outline
(facing connector)