30
9.2 Power Range 2400 VA (208/240 V)
Tower
US 208/240 Model
UT1G2L024C6T
Input
Voltage
208 or 240 VAC (161 – 276 V)
Voltage Range
+15% to -34%
Frequency
50 / 60 Hz auto sensing
Power Factor
Greater than 0.97
Topology
True on-line Double conversion Input PF correction
Output
Voltage
120/208/240 VAC
Capacity (VA)
2400 VA
Capacity (W)
1920 W
Frequency
50 / 60 (45-65) Hz auto sensing *
Wave Form
Sine wave, zero transfer time
Load Power Factor
0.8
Efficiency
AC/DC/AC
Greater than 87%
Rated Current
10 A @ 240V
Overload Capacity
125% for 1 min 130% for 10 sec
Crest Factor
3.0 at full load
Battery
DC Voltage
72V / 12 V (9 AH x 6)
Backup Time
11 min (full load)
Interface
RS-232 and USB standard RemotEye II® and EMD option
Physical
Dimensions
23.2”L x 10.1”W x 27.6”H
Weight
154.3 lbs
Line Cord
None (Hardwired)
Receptacles
None (Hardwired)
Environmen
t
Operating
Temperature
32 – 104°F (0 – 40°C)
Altitude
3300 ft (1000 m) above sea level
Warranty
Three years on electronics
Two years full replacement on battery (See Toshiba warranty policy for
full details.)
• Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user
to select a fixed output frequency and simultaneously disables the bypass mode.
Standards – FCC Part 15 Class A (2-3kVA), UL 1778, ICES-0003
Safety – EN 62040-1, Emissions: EN 62040-2, Immunity: EN 62040-2 Category C2