9.3 Power Range 6000 VA (208/240 V)
1000 Series 6kVA Specification
Specification
Rackmount
US 208/240V
UT1G1G060C6RKB3 + UT1-BR-0607
General
Topology
True on-line, Double conversion, IGBT Power Factor Correction
Input
Certifications
CE
Input
Voltage (V)
Single Phase - 208/240Vin
Capacity (VA)
6kVA
Frequency
45-65 Hz auto sensing
Frequency Synchronization
± 3Hz
Power Factor
Greater than 0.97
Current THD
Less than 15%
Cold Start (0 to 100% load)
Default Output Frequency 60 Hz
Earth leakage (max.)
2mA (UPS only)
Bypass
Voltage (V)
+10/-15% of nominal (default)
+10/-10% of nominal
+15/-20% of nominal
Set by display panel
Output
Voltage
208V or 240V
Voltage Regulations
± 3%
Capacity (W)
4.2kW
Frequency
50 / 60 Hz auto sensing
Battery Mode/Free Run Mode
± 0.25 Hz
Wave Form
Sine wave, zero transfer time
Load Power Factor
0.7 PF
Efficiency AC/DC/AC
Greater than 89% at Nominal Voltage
High Efficiency Mode Efficiency
Greater than 92%
Rated Current (based on 240V)
25.0
Inverter Overload Capacity
125% for 1 min, 150% for 10 sec
Crest Factor
3.0 at full load
Voltage Transient Response
(battery mode with R type load)
0%100%0%; ± 15 % max.
20%100%20%; ± 9 % max.
Voltage Transient Recovery (R
type Load)
Return to nominal voltage within 30 ms
On-line Transfer Time – Inverter to
Bypass and Bypass to Inverter
Less than 4m sec
High Efficiency Transfer Time –
Inverter to Bypass and Bypass to
Inverter
Less than 4m sec transfer time
Short Circuit Protection
Electronic overload and short circuit.
Voltage Total Harmonic Distortion
(Full Linear Load)
Less than 3 % THD
Voltage Total Harmonic Distortion
(Full Non-Linear Load)
Less than 5 % THD
Steady State Output Voltage
Regulation
No-load to Full-load +/- 2% at full battery.
Common Mode Noise
less than 0.5Vrms
Leakage Current
.5mA
Surge Protection
MOV 260 Jules on Output