Toshiba 1000 Power Supply User Manual


 
34
9.5 Backup Time at Partial Loads
Below is the estimated backup time at various fractions of full load for each 1000 Series
model. This table assumes the batteries are fresh and begin with a .full initial charge
Load
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
1000 VA Backup (min)
150
56
38
30
23
19
15
12
10
7
1500 VA Backup (min)
80
37
21
19
18
15
13
11
8
6
2000 VA Backup (min)
150
68
38
26
19
14
11
9
7
6
2400 VA Backup (min)
200
76
53
42
33
28
22
18
15
11
3000 VA Backup (min)
80
40
25
19
15
12
9
8
6
5
6000 VA Backup (min)
45
36
29
22
18
15
13
11
9
7
Table 9.1 Backup Time vs. Partial Load