Toshiba 1000 Power Supply User Manual


 
29
9. Technical Specifications
9.1 Power Range 1000-3000 VA (120 V)
Tower
US 120V Model
UT1A1A010C6
UT1A1A015C6
UT1A1A020C6
UT1A1A030C6
Rack-
mount (2U)
US 120V Model
UT1A1A010C6R
KB2
UT1A1A015C6R
KB2
UT1A1A020C6R
KB2
UT1A1A030C6R
KB2
Input
Voltage
120 VAC (80 144 V)
Voltage Range
+20% to -33%
Frequency
50 / 60 Hz auto sensing
Power Factor
Greater than 0.97
Topology
True on-line Double conversion Input PF correction
Output
Voltage
120 VAC
Capacity (VA)
1000 VA
1500 VA
2000 VA
3000 VA
Capacity (W)
700 W
1050 W
1400 W
2100 W
Frequency
50 / 60 Hz auto sensing *
Wave Form
Sine wave, zero transfer time
Load Power
Factor
0.70
Efficiency
AC/DC/AC
Greater than 86%
Greater than
85%
Rated Current
8.3 A
12.5 A
16.6 A
25 A
Overload
Capacity
125% for 1 min 150% for 10 sec
125% for 1 min
130% for 10
sec
Crest Factor
3.0 at full load
2.5 at full load
Battery
DC Voltage
(Tower & 2U)
36 V / 12 V
9 AH x 3
72V / 12 V
9 AH x 6
Backup Time
(Tower & 2U)
7 min
(full load)
6 min
(full load)
6 min
(full load)
5 min
(full load)
Interface
RS-232 and USB standard RemotEye II® and EMD option
Physical
Dimensions
(Tower)
16.5”L x 6.0”W x 9.4”H
16.7"L x 8.9"W x 14.2"H
Dimensions
(2U)
16.7”L x 16.9”W x 3.5”H
25.0"L x 16.9"W x 3.5"H
Weight
(Tower/2U)
35.6 lbs /
37.6 lbs
37.4 lbs /
37.6 lbs
68.4 lbs /
69.5 lbs
72.6 lbs /
71.5 lbs
Line Cord
5-15P
5-20P
L5-30P
Receptacles
(Tower/2U)
NEMA 5 - 15 P (6 / 6)
Tower - NEMA 5-20 P (12)
2U - NEMA 5-15 P (4)
Environ-ment
Operating
Temperature
32 – 104°F (0 – 40°C)
Altitude
11500 ft (3500 m) above sea level
Warranty
Three years on electronics
Two years full replacement on battery (See Toshiba warranty policy for full
details.)
Output frequency can hard set at 50 or 60 Hz by installing an optional software upgrade. This upgrade enables the user
to select a fixed output frequency and simultaneously disables the bypass mode.
Standards - Safety:UL-1778, Emissions: FCC Part 15 Class B (1000-2000 VA) FCC Part 15 Class A (3000 VA)