5.2. Communication parameters for CCL003Z
Title
Function Description
c100
Communication error detection
delay time
0.0 - 100.0 sec.
c101
Inverter operation at the
communication loss action
0: Stop and controlled by cmod, fmod
1: Operation continue
2: Deceleration stop
3: Coast stop
4: Network error stop (err8 trip)
5: Preset speed operation (by c102 setting)
c102
Preset speed
operation selection
0: None
1 to 15: Preset speed
c103
Communication time-out
condition selection
0: Disconnection detection
1: When communication mode enable (Both cmod and
fmod are set CANopen or communication option) only
2: 1 + Driving operation
c120
*
CC-Link station number
selection
1 to 64
Set the number of stations of inverters (Remote device
station).
c121
*
CC-Link baud rate selection
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
Set the baud rate for CC-LINK network
c122
*
CC-Link extended selection
0: Occupies one station (V1.10)
1: Occupies one station double (V2.0)
2: Occupies one station quadruple (V2.0)
3: Occupies one station octuple (V2.0)
The function of remote registers can be enhanced.