2. Input signal (Inverter -> Master)
The following shows input signals to the master unit. (The output signals for the inverter.)
Device No.. Signal Description
RXn0 Forward running
OFF: Other than forward running
(during stop or reverse rotation)
ON : Forward running
RXn1 Reverse running
OFF: Other than reverse running
(during stop or forward rotation)
ON : Reverse running
RXn2
Output terminal function 1
(RY-RC)
The function depends on output terminal function selection 1
(f130).
RXn3 Output terminal function 2 (OUT)
The function depends on output terminal function selection 2
(f131).
RXn4 Output terminal function 3 (FL)
The function depends on output terminal function selection 3
(f132).
RXn5 Failure FL
OFF : No failure
ON : Failure
RXn6 PI control OFF
OFF :
PI control permitted
ON
: PI control prohibited
RXn7
Acceleration/ deceleration
pattern selection (1 or 2)
OFF: Acceleration/deceleration pattern 1 (AD1)
ON : Acceleration/deceleration pattern 2 (AD2)
RXn8 Emergency stop ON : Emergency stop
RXn9 Coast stop (ST = OFF)
OFF : ST = ON
ON : ST = OFF
RXnA Alarm
OFF: No alarm
ON : Alarm issued
RXnB Reserved* Reserved*
RXnC Monitoring flag
Switched on when the monitored values are set to RWrn,
RWrn+1, RWrn+4 to RWrn+7 by the monitor command
(RYnC) switching on. Switched off when the monitor
command (RYnC) is switched off.
RXnD
Frequency setting completion flag
(RAM)
Switched on when the set frequency is written to the inverter
by the frequency setting command (RYnD) switching on.
Switched off when the frequency setting command (RYnD)
is switched off.
RXnE Reserved* Reserved*
RXnF
Instruction code execution
completion flag
Switched on completion of the processing corresponding to
the instruction code (RWw+2) which is executed when the
instruction code execution request (RYnF) switches on.
Switched off when the instruction code execution completion
flag (RXnF) is switched off.
RX(n+1)0
to RX(n+1)9
Reserved* Reserved*
RX(n+1)A Error status flag
Switched on when occurred an inverter error or option error
(watchdog error, CPU error, ROM error or RAM error).
It is not switched on besides that.
RX(n+1)B Remote station ready
Switched on when the inverter goes into the ready status on
completion of initial setting after power-on or hardware reset.
(Used as an interlock for read/write from/to the master.)
Switched off when an inverter error occurs (protective
function is activated).
RX(n+1)C
to RX(n+1)F
Reserved* Reserved*
"n" is depend on the station number.
* The bit described " Reserved " is unstable. Don't use the “Reserved " bit for the judgment.