E658130
- 17 -
5.5. I/O signal list
5.5.1. One station is occupied (CC-Link Ver.1) (c122=0)
This option occupies one station area of the buffer memory of the PLC.
In the case of c122 = 0, there are remote I/O (RX, RY both 32 bits) and the remote register
(RWw, RWr both 4 word) in the communication data for one station area.
Remote I/O
(Default value = 0)
Inverter (Slave) → PLC (Master) PLC (Master) → Inverter (Slave)
Device No. Signal Device No. Signal
RXn0 Forward running RYn0 Forward rotation command
RXn1 Reverse running RYn1 Reverse rotation command
RXn2 Output terminal 1 (RY-RC) RYn2 Input terminal 3 (S1)
RXn3 Output terminal 2 (OUT) RYn3 Input terminal 4 (S2)
RXn4 Output terminal 3 (FL) RYn4 Input terminal 5 (S3)
RXn5 Failure FL RYn5 Input terminal 6 (S4)
RXn6 PI control OFF RYn6 Input terminal 7 (PIOFF)
RXn7
Acceleration/deceleration
pattern selection (1 or 2)
RYn7 Input terminal 8 (AD1)
RXn8 Emergency stop RYn8 Input terminal 9 (ESTP)
RXn9 Coast stop (ST = OFF) RYn9
Intercept output to inverter
(Coast stop)
RXnA Alarm RYnA Frequency priority CC-Link
RXnB Reserved* RYnB Command priority CC-Link
RXnC Monitoring RYnC Monitor command
RXnD
Frequency setting completion
(RAM)
RYnD
Frequency setting command
(RAM)
RXnE Reserved* RYnE Reserved**
RXnF
Instruction code execution
completion
RYnF Instruction code execution request
RX(n+1)0
to
RX(n+1)9
Reserved*
RY(n+1)0
to
RY(n+1)9
Reserved**
RX(n+1)A Error status flag RY(n+1)A
Error reset request flag
(A reset request is during switched
ON)
RX(n+1)B Remote station ready RY(n+1)B Reserved**
RX(n+1)C
to
RX(n+1)F
Reserved*
RY(n+1)C
to
RY(n+1)F
Reserved**
"n" is depend on the station number.
* The bit described " Reserved " is unstable. Don't use the “Reserved " bit for the judgment.
** Set OFF (“0”) to reserved bit.
Remote register (Default value = 0)
RWr Inverter → PLC RWw PLC → Inverter
Address Signal Address Signal
RWr n Monitor value 1 RWw n Monitor code (1 and 2)
RWr n+1
Monitor value 2
(output frequency)
RWw n+1 Set frequency
RWr n+2 Reply code RWw n+2 Instruction code
RWr n+3 Read data RWw n+3 Write data
"n" is depend on the station number.