E6581343
- 16 -
3.5.1.3. Example 2. Changing the PNU 933 (Control word, bit 11)
AK = 2 (Change parameter value (word))
SPM = 0
PNU = 933 (0x03A5)
PWE = 10 (0x000A)
PKE
0 0 1 0 0 0 1 1 1 0 1 0 0 1 0 1
2 3 A 5
Requirement (PNU 933 = 10 (f111 = 10))
PKW PZD
PKE IND PWE
23 A5 00 00 00 00 00 0A ・・・ ・・・
Response (Value: 0x000D = Inverter over load)
13 A5 00 00 00 00 00 0A ・・・ ・・・
Example of the error occurrence
Requirement (PNU 933 = 136 (out of the value range))
PKW PZD
PKE IND PWE
23 A5 00 00 00 00 00 88 ・・・ ・・・
Response (Value: 0x0002 = Lower or upper limit violated)
73 A5 00 00 00 00 00 02 ・・・ ・・・