E6581343
- 7 -
2.4. Status indicator
The PDP002Z has two LEDs, ST (status) and DX (data exchange) to indicate the
statuses of PROFIBUS-DP and the PDP002Z itself.
ST (Status): Red LED
LED Meanings
Off No diagnostics present
Flashes Waiting for parameterisation or configuration
Lights
DP status error
* For example, a station address is not setcorrectly.
DX (Data exchange): Green LED.
Indicates the status of the PROFIBUS network.
It lights when the PDP002Z is on-line and data exchange is possible.
2.5. Communications-related parameters
Parameter Function Adjustment range Default setting
f830* Communication
option setting 1
(PPO TYPE)
0: None
1: PPO TYPE 1
2: PPO TYPE 2
3: PPO TYPE 3
4: PPO TYPE 4
0
f831
-
f846
Communication option
setting 2 - 13
Refer to section 4. 0
f851 Inverter operation at
the communications
loss action
(Network wire breaks)
0: Stop and break of connection
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command
(Operating at the preset speed operation
frequency set with f852)
0
f852 Preset speed
operation selection
0: None
1 to 15: Preset speed
0
f853 Monitoring of
communication
device station
address
Displays the station address assigned with the
DIP switch.
0 to 125
2
f854** Monitoring of
communications
device’s baud rate
Displays the network communication speed set
with the DIP switch.
0: 12 Mbit/s
1: 6 Mbit/s
2: 3 Mbit/s
3: 1.5 Mbit/s
4: 500 kbit/s
5: 187.5 kbit/s
6: 93.75 kbit/s
7: 45.45 kbit/s
8: 19.2 kbit/s
9: 9.6 kbit/s
255: Disabled
0
* When the parameters are changed, the power must be cycled to the VF-AS1/PS1 for
the changes to take effect.
** The baud rate of the PDP002Z is automatically set by configuration a baud rate for the
master.