4.2.16. FC91 (Alarm code)
bit Function 0 1 Note
0 Over current alarm Normal Under alarm c” blinking
1 Inverter over load alarm Normal Under alarm l” blinking
2 Motor over load alarm Normal Under alarm l” blinking
3 Over heat alarm Normal Under alarm h” blinking
4 Over voltage alarm Normal Under alarm p” blinking
5 Under voltage of main power Normal Under alarm -
6 (Reserved) - - -
7 Under current alarm Normal Under alarm -
8 Over torque alarm Normal Under alarm -
9 OLr alarm Normal Under alarm -
10 Cumulative run-time alarm Normal Under alarm -
11 (Reserved) - - -
12 (Reserved) - - -
13 (Reserved) - - -
14 Stop after instantaneous power off - Dec., Under stop Refer to f256 value
15 Stop after LL continuance time - Dec., Under stop Refer to uvc value
4.2.17. FD06 (Input TB Status)
bit TB Name Function (Parameter) 0 1
0 F Input TB Function select 1 (f111)
1 R Input TB Function select 2 (f112)
2* ST Input TB Function select 3 (f113)
3 RES Input TB Function select 4 (f114)
4 S1 Input TB Function select 5 (f115)
5 S2 Input TB Function select 6 (f116)
6 S3 Input TB Function select 7 (f117)
7 S4 Input TB Function select 8 (f118)
8 L1 Input TB Function select 9 (f119)
9 L2 Input TB Function select 10 (f120)
10 L3 Input TB Function select 11 (f121)
11 L4 Input TB Function select 12 (f122)
12 L5 Input TB Function select 13 (f123)
13 L6 Input TB Function select 14 (f124)
14 L7 Input TB Function select 15 (f125)
15 L8 Input TB Function select 16 (f126)
OFF ON
This function is reserved in VF-PS1 and VF-AS1(WN1/WP1).
4.2.18. FD07 (Output TB Status)
bit TB Name Function (Parameter) 0 1
0 OUT1 Output TB Function select 1 (f130)
1 OUT2 Output TB Function select 2 (f131)
2 FL Output TB Function select 3 (f132)
3 OUT3 Output TB Function select 4 (f133)
4 OUT4 Output TB Function select 5 (f134)
5 R1 Output TB Function select 6 (f135)
6 OUT5 Output TB Function select 7 (f136)
7 OUT6 Output TB Function select 8 (f137)
8 R2 Output TB Function select 9 (f138)
9 R3 Output TB Function select 10 (f168)
10 R4 Output TB Function select 11 (f169)
OFF ON
11 - 15 - - - -