PREINSTALLATION
Environmental and electrical requirements
Your LPS has important environmental and electrical requirements
that must be accommodated. Table 1-3 defines the environment
requirements.
Table 1-3. LPS environmental requirements
Environmental condition Requirement
Operating Temperature Recommended: 72°F ± 4°F (22° C ±2°
C)
Minimum: 60°F/15.5°C
Maximum: 80°F/26.7°C
Humidity Recommended: 45 ± 10%
Minimum: 30%
Maximum: 65%
Heat dissipation, printer
system controller
peripheral cabinet
Operating: 14,980 Btu per hour
Standby: 7,370 Btu per hour
Operating: 4,450 Btu per hour
Standby: 4,450 Btu per hour
Operating: 3,195 Btu per hour
Standby: 3,195 Btu per hour
XEROX 4890 HIGHLIGHT COLOR LPS INSTALLATION PLANNING REFERENCE 1-19