AMX RE-DM6 Switch User Manual


 
Installation
21
RE-DM4 and RE-DM6 RADIA Eclipse Dimmer Modules
Connecting high-voltage input power and loads
Follow these steps to wire high-voltage (120 VAC and 240 VAC) power connections (FIG. 19) to any of
the AMX Lighting modules
1. Connect the green ground wire(s) to the copper ground lug on the enclosure. Ensure the ground wire
is properly connected to earth ground.
2. Connect the white neutral wire(s) to one of the terminals on the enclosure's neutral terminal block.
3. Provide a separate neutral wire for each controlled zone.
4. Connect the black line input from the electrical panel to the enclosure's line terminal. The line input
terminal accepts a 0 AWG copper conductor.
5. Connect load lines from the electrical devices to the Load terminals. Load 1 applies to dimmer 1,
Load 2 applies to dimmer 2, and so on.
RDA-ENC6B 120/208 VAC line input (three phase)
FIG. 20 shows a 120/208 VAC three-phase (4 W + G) wiring diagram for the RDA-ENC6B line input
terminal block.
FIG. 19 High-voltage, three-phase input power
FIG. 20 RDA-ENC6B 120/208 VAC three-phase (4 W + G) wiring diagram
12a2b3
RDA-ENC6B
C
onnect to neutral block
line input terminal
These
connections
are factory-
wired
12a2b3