Total power off – isolating one UPS in a parallel system.
Parallel system – turning the isolated UPS into normal operation.
From the UPS: From the Main Menu screen
select Status and scroll down to Status of
actual redundancy: n+ in order to check that
the remaining UPS(s) will be able to carry the
load when one UPS is isolated.
From the UPS: Turn load OFF from the display
on the UPS to be isolated via Control–Turn
Load off–Yes, turn Load off.
From the external MBP: Check that the output
lamp
(Q002) of the UPS to be isolated is lit.
From the external MBP: Turn the output
switch
(Q002) connected to the UPS you want
to isolate to position “0”
(OFF).
From the external MBP: Turn the input switch
(Q001) connected to the UPS you want to
isolate to position “0”
(OFF) .
From the XR Enclosure(s) (if available): Set
the DC disconnect switch (if available) on the
XR Enclosure to the
OFF position.
From the UPS: Disconnect the batteries in the
UPS which you want to isolate by pulling them
out to the red disconnect line.
From the XR Enclosure(s) (if available):
Disconnect the batteries by pulling them out to
the red disconnect line.
From the external MBP: Turn the input switch
(
Q1) connected to the UPS you want to turn
into normal operation to position “1”
(ON).
From the UPS: Connect the batteries by
pulling them in.
From the XR Enclosure(s) (if available):
Connect the batteries by pulling them in.
From the XR Enclosure(s) (if available): Set
the DC disconnect switch (if available) on the
XR Enclosure to position
ON.
From the external MBP: Turn the output
switch
(Q002) connected to the UPS you want
to turn into normal operation to position “I”
(ON).
From the UPS: Turn load ON from the display
on the UPS you want to turn into normal
operation via Control–Turn Load on–Yes,
turn Load on.
From the UPS: Press ESC two times to get back
to the Overview Screen.
From the UPS: On the Overview Screen, check
that the load percentage of the UPS units is
approximately the same.