APC VT Power Supply User Manual


 
Maintenance – Parts Replacement
30 Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation 990-2282A-001
How to remove and install battery locks (if available). If your system is equipped with Battery
Locks, follow the below procedure to remove the battery locks.
Remove the M6 screw attaching the battery
lock to the shelf.
Push the battery lock to the left, push it
upwards and remove.
Use reverse procedures for installation of
battery locks.
Replacement.
Directions for replacement.
APC recommends that a whole battery module (four batteries) is replaced
at the same time to ensure optimal runtime (see Example 1). However, it is only necessary to replace two
batteries at the same time according to Example 2 and 3 in the below tables.
Caution
Batteries must be replaced by trained personnel only (see the section General safety
prior to Battery Module replacement).
523mm/(20in)
Enclosure
Col A Col B Col C Col D
Example 1
New New New New
Example 2
New New Old Old
Example 3
Old Old New New
352mm/(14 in)
Enclosure
Col A Col B
Example 1
New New
New New
Example 2
New New
Old Old
Example 3
Old Old
New New