APC 78-10169-02 Computer Monitor User Manual


 
2-25
Cisco ICS 7750 Administration and Troubleshooting Guide
78-10169-02 Rev. B0
Chapter 2 Monitoring the System
Monitoring a UPS
Step 17 In the left pane of the browser window, choose Smart-UPS 1400 RM XL >
PowerChute.
Step 18 In the Add Client IP Address field, enter the IP address of the SPE running
System Manager.
Step 19 Click Add.
The IP address that you entered in Step 18 and Step 19 will appear in the
Configured Client IP Addresses pane.
Step 20 In the left pane of the browser window, choose Network > SNMP.
Step 21 In the SNMP table, verify that the Access field is set to enabled.
Step 22 Click Apply.
Step 23 In the Trap Receiver table, enter the UPS IP address in the Public field.
Step 24 Click Apply.
Step 25 In the Access Control table, enter the UPS IP address in the Private and Public
fields.
Step 26 Click Apply.
Step 27 In the left pane of the browser window, choose Event Log.
The UPS reports its status in the Event column. Text similar to the following will
be displayed:
Management Card: Web User apc logged in from <IP address>
Step 28 Unplug the UPS power cord.
The UPS emits an audio tone.
Step 29 Plug the UPS power cord in again.
In the Event column of the Event Log, text similar to the following will be
displayed:
UPS: Switched to battery backup power, utility power failure.
UPS: Returned from battery backup power, utility power restored.
Step 30 Choose Start > Run.
Step 31 Open a Telnet session with the SPE running System Manager:
telnet
IP address
5000