Barco SF-10V Projector Accessories User Manual


 
3. Installation requirements
3.2 Electrical requirements for the SF-10V display
Power requirements
One SF-10Vtile requires220-240 VAC,50-60 Hz, 5.72amps at 230VAC.Note thatone SF-10V tile correspond with adisplay surface
of 1,23 m². Power link cables are used to link the power from tile to tile. However, MAXIMUM two (2) tiles, may be connected in
parallel. So, one power source cable has to be provided per two (2) tiles. Every power source cable should be protected by a circuit
breaker or fuses rated 16 A / 250 VAC (15 A / 250 VAC in the USA and Canada).
Barco provides a range of pow er boxes, which me et the requiremen ts of your SF-10V d isplay. Contact B
arco
for more information about power boxes and power requirements for your SF-10V display.
Power system
It is recommended to use a TN-S power distribution system (a power distribution system with a separate neutral and grounding
conductor) in order to avoid large ground current loops due to voltage differences in the neutral conductor. The total electrical
installation shouldbe protectedby an appropriately rateddisconnect switch, circuitbre
akers, overvoltage protector andGround Fault
Current Interrupters. The installation shall be done according to the local electrical installation codes. In Europe special attention
should be given to EN 60364, the standard for electrical installation of buildings. In Germany VDE 0100 should be adhered to. In
America, special attention should be given to the National Electrical Code, ANSI/NF
PA 70.
This equipment MUST be earthed
In order to protect against risk of electric shock, the installation should be properlygrounded. Defeating the purpose of the grounding
type plug will expose you to the risk of electric shock.
14
R59770542 SF-10V DISPLAY 10/02/2012