Compaq MTEK6000 Network Router User Manual


 
MTEK6000 SERIES USER'S MANUAL
C - 4 January 2002
Flow Units
The flow units parameter reflects the time
used to represent the flow rate. For example,
if the flow rate represents cubic feet per hour,
this parameter should be set to Hour. The
Default value is 2.
Minute 1
Hour 2
Day 3
Gas Day Roll Time HHMM (Hours,
Minutes)
This item is used in Daily and Monthly
history modes to determine when the gas day
ends. The time is entered in military time.
For example, a standard roll time of 8:00AM
is entered as 800.0. The Range is 0 to 2359.
The default value is 800.
High Differential Pressure Alarm Setpoint
The setpoint at which the unit determines that
there is a High Differential Pressure alarm
condition. The Default value is 1500.
High Differential Pressure Alarm Reset
After a High Differential Pressure alarm
occurs, the setpoint at which the unit exits this
condition is entered in this location. The
Default value is 1480.
High Flow Rate Alarm Reset
After a High Flow Rate alarm occurs, the
setpoint at which the unit exits this condition
is entered in this location. The Default value
is 99,990.
High Flow Rate Alarm Setpoint
The setpoint at which the unit determines that
there is a High Flow Rate alarm condition.
The Default value is 100,000.
High Pressure Alarm Setpoint
The setpoint at which the unit determines that
there is a High Pressure alarm condition. The
Default value is 1500.
High Pressure Alarm Reset
After a High Pressure alarm occurs, the
setpoint at which the unit exits this condition
is entered in this location. The Default value
is 1480.
High Temperature Alarm Reset
After a High Temperature alarm occurs, the
setpoint at which the unit exits this condition
is entered in this location. The Default value
is 180.
High Temperature Alarm Setpoint
The setpoint at which the unit determines that
there is a High Temperature alarm condition.
The Default value is 200.
Low Differential Pressure Alarm Reset
After a Low Differential Pressure alarm
occurs, the setpoint at which the unit exits this
condition is entered in this location. The
Default value is -80.
Low Differential Pressure Alarm Setpoint
The setpoint at which the unit determines that
there is a Low Differential Pressure alarm
condition. The Default value is -100.
Low Flow Rate Alarm Reset
After a Low Flow Rate alarm occurs, the
setpoint at which the unit exits this condition
is entered in this location. The Default value
is -80.
Low Flow Rate Alarm Setpoint
The setpoint at which the unit determines that
there is a Low Flow Rate alarm condition.
The Default value is -100.
Low Pressure Alarm Reset
After a Low Pressure alarm occurs, the
setpoint at which the unit exits this condition
is entered in this location. The Default value
is -80.