Delta Electronics VFD-XXXE Network Card User Manual


 
English- 25
Pr. Explanation Settings
Factory
Setting
NOTE
08.17 Auto Energy Saving
0: Disable
1: Enable
0
08.18 AVR Function
0: AVR function enable
1: AVR function disable
2: AVR function disable for decel.
3: AVR function disable for stop
0
08.19
Software Brake
Level
115V / 230V series: 370.0to 430.0V
460V series: 740.0 to 860.0V
380.0
760.0
a08.20
Compensation
Coefficient for Motor
Instability
0.0~5.0
0.0
08.21 OOB Sampling Time 0.1 to 120.0 sec 1.0
08.22
Number of OOB
Sampling Times
00 to 32 20
08.23
OOB Average
Sampling Angle
Read only #.#
08.24 DEB Function
0: Disable
1: Enable
0
08.25 DEB Return Time 0 to 250 sec 0
Group 9 Communication Parameters
a09.00
Communication
Address
1 to 254 1
a09.01 Transmission Speed
0: Baud rate 4800bps
1: Baud rate 9600bps
2: Baud rate 19200bps
3: Baud rate 38400bps
1
a09.02
Transmission Fault
Treatment
0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and keep operating
3
a09.03 Time-out Detection
0.1 ~ 120.0 seconds
0.0: Disable
0.0
a09.04
Communication
Protocol
0: 7,N,2 (Modbus, ASCII)
1: 7,E,1 (Modbus, ASCII)
2: 7,O,1 (Modbus, ASCII)
3: 8,N,2 (Modbus, RTU)
4: 8,E,1 (Modbus, RTU)
5: 8,O,1 (Modbus, RTU)
6: 8,N,1 (Modbus, RTU)
7: 8,E,2 (Modbus, RTU)
8: 8,O,2 (Modbus, RTU)
9: 7,N,1 (Modbus, ASCII)
10: 7,E,2 (Modbus, ASCII)
11: 7,O,2 (Modbus, ASCII)
0
09.05 Reserved
09.06 Reserved
a09.07
Response Delay
Time
0 ~ 200 (unit: 2ms)
1