Delta Electronics VFD-XXXE Network Card User Manual


 
English- 28
Pr. Explanation Settings
Factory
Setting
NOTE
11.00
Multi-function
Output Terminal
MO2/RA2
0
11.01
Multi-function
Output Terminal
MO3/RA3
0
11.02
Multi-function
Output Terminal
MO4/RA4
0: No function
1: AC drive operational
2: Master frequency attained
3: Zero speed
4: Over torque detection
5: Base-Block (B.B.) indication
6: Low-voltage indication
7: Operation mode indication
8: Fault indication
9: Desired frequency 1 attained
10: Terminal count value attained
11: Preliminary count value attained
12: Over Voltage Stall supervision
0
11.03
Multi-function
Output Terminal
MO5/RA5
0
11.04
Multi-function
Output Terminal
MO6/RA6
0
11.05
Multi-function
Output Terminal
MO7/RA7
13: Over Current Stall supervision
14: Heat sink overheat warning
15: Over Voltage supervision
16: PID supervision
17: Forward command
18: Reverse command
19: Zero speed output signal
20: Warning(FbE,Cexx, AoL2, AUE, SAvE)
21: Brake control (Desired frequency
attained)
22: Drive ready
23: Desired frequency 2 attained
0
0
11.06
Multi-function Input
Terminal (MI7)
0: No function
1: Multi-Step speed command 1
2: Multi-Step speed command 2
3: Multi-Step speed command 3
0
11.07
Multi-function Input
Terminal (MI8)
0
11.08
Multi-function Input
Terminal (MI9)
0
11.09
Multi-function Input
Terminal (MI10)
0
11.10
Multi-function Input
Terminal (MI11)
0
11.11 Multi-function Input
Terminal (MI12)
4: Multi-Step speed command 4
5: External reset
6: Accel/Decel inhibit
7: Accel/Decel time selection command
8: Jog Operation
9: External base block
10: Up: Increment master frequency
11: Down: Decrement master frequency
12: Counter Trigger Signal
13: Counter reset
14: E.F. External Fault Input
15: PID function disabled
16: Output shutoff stop
17: Parameter lock enable
18: Operation command selection (external
terminals)
19: Operation command selection (keypad)
20: Operation command selection
(communication)
21: FWD/REV command
22: Source of second frequency command
23: Run/Stop PLC Program (PLC1) (NOT
for VFD*E*C models)