Delta Electronics VFD-XXXE Network Card User Manual


 
English- 27
Pr. Explanation Settings
Factory
Setting
NOTE
10.00
PID Set Point
Selection
0: Disable PID operation
1: Keypad (based on Pr.02.00)
2: 0 to +10V from AVI
3: 4 to 20mA from ACI or 0 to +10V from
AVI2
4: PID set point (Pr.10.11)
0
10.01
Input Terminal for
PID Feedback
0: Positive PID feedback from external
terminal AVI (0 ~ +10VDC)
1: Negative PID feedback from external
terminal AVI (0 ~ +10VDC)
2: Positive PID feedback from external
terminal ACI (4 ~ 20mA)/ AVI2 (0 ~
+10VDC).
0
10.01
Input Terminal for
PID Feedback
3: Negative PID feedback from external
terminal ACI (4 ~ 20mA)/ AVI2 (0 ~
+10VDC).
0
a10.02
Proportional Gain
(P)
0.0 to 10.0 1.0
a10.03 Integral Time (I)
0.00 to 100.0 sec (0.00=disable)
1.00
a10.04
Derivative Control
(D)
0.00 to 1.00 sec
0.00
10.05
Upper Bound for
Integral Control
0 to 100% 100
10.06
Primary Delay Filter
Time
0.0 to 2.5 sec 0.0
10.07
PID Output Freq
Limit
0 to 110% 100
10.08
PID Feedback
Signal Detection
Time
0.0 to 3600 sec (0.0 disable) 60.0
10.09
Treatment of the
Erroneous PID
Feedback Signals
0: Warn and RAMP to stop
1: Warn and COAST to stop
2: Warn and keep operation
0
10.10
Gain Over the PID
Detection Value
0.0 to 10.0 1.0
a10.11
Source of PID Set
point
0.00 to 600.0Hz
0.00
10.12 PID Offset Level 1.0 to 50.0% 10.0
10.13
Detection Time of
PID Offset
0.1 to 300.0 sec 5.0
10.14
Sleep/Wake Up
Detection Time
0.0 to 6550 sec 0.0
10.15 Sleep Frequency 0.00 to 600.0 Hz 0.00
10.16 Wakeup Frequency 0.00 to 600.0 Hz 0.00
10.17
Minimum PID
Output Frequency
Selection
0: By PID control
1: By minimum output frequency (Pr.01.05)
0
Group 11 Parameters for Extension Card