Eaton Electrical 9120 Power Supply User Manual


 
14
5.7 Relay Card
This interface provides true relay contact output to peripheral devices. Outputs are user-selectable
as normally open or normally closed.
Table 2. Relay Card (AS/400) Pin Assignment
Pin Number Signal Name Definition Direction
1 - Isolated common to pins 2 & 3 -
2 Line OK Relay contact; closed to pin 1 -
3 Line Failure Relay contact; closed to pin 1 -
4 - Isolated common to pins 5 & 6 -
5 Battery Normal Relay contact; closed to pin 4 -
6 Battery Low Relay contact; closed to pin 4 -
7 - Isolated common to pins 8 & 9 -
8 UPS Alarm Relay contact; closed to pin 7 -
9 UPS On/OK Relay contact; closed to pin 7 -
10 - Isolated common to pins 11 & 12 -
11 UPS Online/Inverter Relay contact; closed to pin 10 -
12 UPS on Bypass Relay contact; closed to pin 10 -
13 +12VDC Signal supply +12VDC Out
14 Signal GND Signal ground - Common -
15 UPS Shutdown Minimum 5 seconds high level In
signal (+12VDC) to perform
shutdown according to following
Relay Card Jumper settings:
JP1 (default) JP2 JP3
UPS Normal - No response Go to bypass mode,
back online when
shutdown pins opened
UPS on Battery Output off after Immediate output off Immediate output off
120 sec. Back online UPS shutdown in UPS shutdown in
on resumption of AC 12 seconds 12 seconds
power
6.0 Installing Lansafe Software
Your UPS is supplied with a CD-ROM and communication cable to install and operate Lansafe power man-
agement software. To install Lansafe on your computer, follow the instructions enclosed with the Software
Suite CD-ROM.