58 Chapter 8 Specifications
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Chapter 8 Specifications
This chapter provides the specifications of the HIPULSE U UPS.
8.1 Conformity And Standard
Table 8-1 Conformity and standard
Description Year Normative references
Safety requirements 1999 IEC60950-1, IEC62040-1-1, UL1778
EMC 2005 IEC/EN62040-2
Design and test methods 1999 IEC62040-3
8.2 Environmental Requirements
Table 8-2 Environmental requirements
Power rating (kVA)
Item Unit
160 200 300 400
Operating Temperature °C 0~40
Maximal temperature for 8hr day °C 40°C (derate power by 1.5% per °C between 40°C and 50°C
Mean Temperature for 24hr °C Maximally 35
Relative humidity - ≤95% at 20°C
Altitude of operation m ≤1000m asl (derate power by 1% per 100m between 1000m and 2000m)
Storage temperature and transport
temperature
°C -25 to 70
8.3 Mechanical Characteristics
Table 8-3 Mechanical characteristics
Power rating (kVA)
Item Unit
160
(6-pulse)
160
(12-pulse)
200
(6-pulse)
200
(12-pulse)
300
(6-pulse)
300
(12-pulse)
400
(6-pulse)
400
(12-pulse)
Height mm 1900
Width mm 1250 1640 1250 1640 1640 2280 2280 2280
Depth mm 875
Weight kg 1200 1725 1350 2000 1600 2200 2100 2750
Ventilation - By internal intake fans
Airflow m
3
/h 2590 2750 2750 2910 5350 5350 6150 6150
Cable entry - Bottom or either side (top optional)
8.4 Electrical Characteristics (Input Rectifier)
Table 8-4 Electrical characteristics (input rectifier)
Power rating (kVA)
Item Unit
160
(6-pulse)
160
(12-pulse)
200
(6-pulse)
200
(12-pulse)
300
(6-pulse)
300
(12-pulse)
400
(6-pulse)
400
(12-pulse)
Rated mains voltage Vac
380
, 400, or 415
Supply - Three phase without neutral
Input voltage
tolerance
1
% ±15, (maxmally, from 290Vac to 498Vac)
Frequency Hz
50
or 60
Input frequency
tolerance
Hz 45~65