Chapter 8 Specifications 59
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
Power rating (kVA)
Item Unit
160
(6-pulse)
160
(12-pulse)
200
(6-pulse)
200
(12-pulse)
300
(6-pulse)
300
(12-pulse)
400
(6-pulse)
400
(12-pulse)
Rated input power
2
kVA 197 191 245 236 365 354 488 469
Rated input current
2
A 298 289 371 358 551 535 739 708
Maximal input Power
3
kVA 246 239 306 295 420 407 609 584
Maximal input
current
3
A 373 362 464 447 634 616 931 885
Duration of
progressive power
walk-in
4
s 5~300
Note:
1. With mains at -15% and suggested battery elements the UPS maintains the output rated voltage at rated load but cannot
guarantee float charge to battery; the battery does not discharge.
2. IEC62040-3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery.
3. IEC62040-3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed
current.
4. Set by dedicated background software
8.5 Electrical Characteristics (DC Intermediate Circuit)
Table 8-5 Electrical characteristics (DC intermediate circuit)
Power rating (kVA)
Item Unit
160 200 300 400
Voltage range for inverter operation Vdc 320~490
Recommended number of lead-acid cells
1
,
2
pcs
192 (380Vac)
198 (400Vac)
204 (415Vac)
Recommended float charge voltage 2.25V/el.
1
Vdc
432 (380Vac)
446 (400Vac)
459 (415Vac)
Recommended boost charge voltage 2.35V/el.
1
Vdc
451 (380Vac)
465 (400Vac)
479 (415Vac)
Maximum voltage on manual charge 2.40 V/el.
1
Vdc
461 (380Vac)
475 (400Vac)
490 (415Vac)
End-of-discharge voltage 2.45V/el.
1
Vdc
471 (380Vac)
485 (400Vac)
500 (415Vac)
Max boost charge duration
3
min 480~1800
Freshening charge duration
3
h 1~36
Boost-float threshold current
3
A 0.001C~0.025C
Ripple voltage superimposed
4
% ≤1
Note:
1. (According to rated voltage).
2. Factory set for rated 380V, different cells number and voltage per cell may be set by configuration software.
3. Set by software.
4. Battery disconnected, RMS percentage value referred to DC voltage