Emerson 381333234 E Surge Protector User Manual


 
CONTROL FEATURES (continued)
5-- 3
How to Set Optional Programmable Engine Exerciser (Accessory 11CD)
Proceed with care! The automatic transfer
switching equipment is energized.
Setting the Clock (Time and Day)
Step Press Button Display Meaning
1 reset
1234567 (blink)
00 00
¬ f
after self-test,
clears memory
2
hold h,then
press ±1h
1234567
AM 12 00
¬ f
military 24 hr
or AM/PM
12 hr time
Note Repeat step 2 to toggle between
military (blank display) and AM/PM time.
3
hold ¬
(clock symbol)
1234567 (blink)
00 00
¬ f
hold ¬ while
setting thru
step 7
4
±1h once
(if Daylight
Saving Time)
±1h
do nothing if it
is Standard
Time.
5
h (hold for
fast count)
[00] 00 hour
6
m (hold for
fast count)
00 [00] minute
7
Day Mo Tu We Th Fr
Sa Su
day
8 release ¬ :blinking
time & date set,
clock starts
Programming Engine On-Off Period(s)
Step Press Button Display Meaning
1
Prog.
(do not
hold)
1234567
–– : ––
begin
2 hand ¬ on
3 h start hour
4 m s tart minute
start engine
5 Day start day
g
Note Successive pressing displays blocks of days:
Mon–Sat, Mon–Fri, Sat & Sun (1 is Monday)
6
Prog. 1234567
–– : ––
begin
7
Press hand
(2 times)
f
off
8 h stop hour
9 m stop minute
stop engine
10 Day stop day
p
g
11 ¬ :blinking program set
display
clock
button
Figure 5-2. Exerciser display and push buttons
program
button
±1h
button
hour
button
minute
button
day
button
reset
button
on/off button
Changing or Checking Time Programs
By operating the Prog. button, the individual commands
as programmed can, at any time, be brought consecutively
into the display for revision or checking. Revisions are
accomplished by programming over the existing programs
using the steps at the left.
Canceling Time Programs
After the selecting the desired program, use the h and
m buttons to set hours and minutes to zero; the ––:–– will
be displayed. This program has been made ineffective
and will no longer be carried out. To cancel all programs,
press the Res. (reset) button. This clears all memory
including the time base and program storage.
Manual Override
Do not manually override the exerciser unless you
are sure that the controller has been set for
exercisewithoutload(seepage52).Failuretodo
so could result in possible injury if the transfer
swi tc h operate s whi l e the en c l osur e door i s op e n.
Step Press Button Display Meaning
1 hand ¬ hand on
2 hand [ ¬ ] permanent on
3 hand [ f ] permanent off
4 hand ¬ f back to automatic
Daylight Savings / Standard Time Change
To change toDaylight Savingstime (Summertime), pressthe
¦1h button once. Clock advances by one hour a nd +1h
appears in display.
To change to Standard Time (Greenwich mean time in UK,
Middle European time in Germany), press the ¦1h button
agai n; the clock sets back one hour a nd +1h disappears.