Emerson 50 and 60 Hz Power Supply User Manual


 
Operating Procedures
89
7.9 Shutdown Procedure—Complete UPS and Load Shutdown
This procedure must be followed to completely power down the UPS and LOAD. All power switches,
isolators and circuit breakers will be opened and power will be removed from the load.
In multi-module systems – perform each step of the procedure in every UPS module before proceeding
to the next step.
1. Press the EPO (Emergency Power Off) button at the UPS front panel only. This will disable
Rectifier, Inverter, Static Switch and Battery operation. The Load will be de-energised.
2. Open the UPS door to gain access to the main power switches.
3. Open the Rectifier input power switch Q1
4. Open external battery circuit breaker (where an external battery is used). This breaker is located
inside the battery cabinet (if used) or is otherwise adjacent to the battery racks
5. Open Output power switch Q5
6. Open bypass input power switch Q2
7. Ensure maintenance bypass power switch Q3 is open.
8. All mimic panel LED indications and messages will extinguish as the mains driven internal
power supplies decay.
9. To completely isolate the UPS from the AC supplies, the main external power input isolator (both
isolators, where split supplies are provided for rectifier and bypass) and external output isolator
must be opened and tagged with warning labels accordingly.
7.10 Emergency Shutdown With EPO
This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The
system will turn off the rectifier, inverter and stop powering the load immediately (including the
inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS’s controls will remain active; however, the output will be
turned off. To remove all power from the UPS, the external feeder breaker should be opened.
!
CAUTION
The following procedure will switch off all power to the load equipment.
NOTE
Except in an emergency situation, do not press any remote EPO button.
!
WARNING
Hazardous Battery Voltage
No operator serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorised to remove such covers.
The UPS battery and connecting terminals remains energized at hazardous voltage levels at
all times. The battery is located behind protective covers that require a tool for their removal:
inside the UPS cabinet (30 and 40kVA models), inside a free-standing battery cabinet or on
open racks inside a dedicated battery room that may be locked.