Emerson 50 and 60 Hz Power Supply User Manual


 
Operator Control Panel and Display
101
Inv. turned Off Manually Manual Turn Off via front panel
EPO Emergency Power Off direct access key pressed or external command received
Transfer Confirm
Prompt to press “enter” key to acknowledge that an interrupted load transfer to
bypass will happen.
Transfer Cancel
Prompt to press “ESC” key to avoid that an interrupted load transfer to bypass will
happen.
Unit Off Confirm
Prompt to press “enter” key to acknowledge that the UPS will be disconnected from
other paralleled UPS modules.
System Off Confirm
Prompt to press “enter” key to acknowledge that the all paralleled UPS will be
disconnected from the load.
Fault Reset Fault clear direct access key pressed
Alarm Silence Silence On/Off direct access key pressed
Turn On Fail
Inverter failed to turn on when Inverter On direct access key was pressed. This may
be as a result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier
not ready.
Alarm Reset Fault clear or Silence On/Off direct access key pressed
Bypass Mode Load supplied from AC input bypass supply.
Normal Mode
Load supplied from Inverter output through double conversion of the AC mains input
supply.
Battery Mode Load supplied from Inverter output through double conversion of the Battery supply.
Source share mode
Load supplied from Inverter output through shared double conversion of the AC
mains input supply and of the Battery supply.
UPS Shutdown UPS Shutdown, output power-down
Check UPS Output Inverter off during normal startup (diagnostics information only)
Generator Connected
Generator active signal received. Source share mode may be activated pending
UPS settings.
BCB open Battery Circuit Breaker status (open)
BCB closed Battery Circuit Breaker status (closed)
Battery Float Charging Battery status (Float charge mode)
Battery Boost Charging Battery status (Boost charge mode)
Battery Discharging Battery status (discharge mode)
Battery Period Testing Automatic periodic battery maintenance discharge test (20% capacity discharge)
Batt. Capacity Testing User initiated battery capacity discharge test (100% capacity discharge)
Batt. Maint. Testing User initiated maintenance discharge test (20% capacity discharge)
UPS System Testing User initiated UPS self test
Inverter in Setting Inverter starting up and synchronising
Rectifier in Setting Rectifier starting up and synchronising
MBP-T cabinet Fan Fault Maintenance bypass cabinet fans fault.
Ext Input TX Overtemp External Input Isolation Transformer Over Temperature
Ext Output TX Overtemp External Output Isolation Transformer Over Temperature
Battery Room Alarm Environment in Battery Room Needs Attention
Rotary Sw. Test Pos. Rotary switch is in test position.
Rotary Sw. Normal Pos. Rotary switch is in normal position.
Rotary Sw. Bypass Pos. Rotary switch is in bypass position.
Rotary Sw. Maint. Pos. Rotary switch is in maintenance position.
Battery Contactor Open Battery Contactor Open
Battery Contactor Close Battery Contactor Closed
Battery Reverse Connect the battery again and check the wiring of batteries
No Battery Check the battery and the wiring of batteries
Table 23 UPS messages
Message Description / Suggested Action (if any)