Emerson AXP1600 Power Supply User Manual


 
Emerson and Pigeon Point OEM Commands Supported IPMI Commands
AXP1406/AXP1600 Subsystem IPMI Programmer’s Reference (6806800B66C)
23
This command requests a SAM switchover.
This command instructs the SAM to transition a FRU to the M0 (not installed) state.
Table 1-16 Shelf Manager Switchover (Cmd = 0x02)
Byte Data field
Request data 1 Pigeon Point Systems IANA Enterprise number, LSB first
2 0x0A
3 0x40
0x00
4 Flags
0x00 Switchover, but do not reboot the active Shelf Manager
0x01 Switchover, and reboot the active Shelf Manager
Response data 1 Completion Code
2 0x0A
3 0x40
4 0x00
Table 1-17 Set FRU Extracted (Cmd = 0x03)
Byte Data field
Request data 1 Pigeon Point Systems IANA Enterprise number, LSB first
2 0x0A
3 0x40
0x00
4 IPMB address
5FRU Id
6 Force option
0x00 Only extract specified FRU if it is in M7 state
0x01 Extract the specified FRU regardless of its current state
Response data 1 Completion Code
2 Pigeon Point Systems IANA Enterprise number, LSB first
3 0x0A
4 0x40
0x00