13.0 SYSTEM DATA
Table 2 Liebert Challenger ITR air-cooled data—60 Hz
System Type
BR = Horizontal Flow
Self-Contained
Split Systems
w/Outdoor Prop-Fan
Condensing Unit
w/Indoor Centrifugal
Condensing Unit
Indoor Unit BR 067A BR 060E BR 060E
Net Capacity Data BTU/H kW BTU/H kW BTU/H kW
100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH
Total 78,100 22.9 76,200 22.3 73,200 21.4
Sensible 78,100 22.9 76,200 22.3 73,200 21.4
Non Standard Flow Rates 2400 CFM 2300 CFM 2100 CFM
95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH
Total 77,500 22.7 75,800 22.2 73,000 21.4
Sensible 77,500 22.7 75,800 22.2 73,000 21.4
Non Standard Flow Rates 2700 CFM 2500 CFM
90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH
Total 73,600 21.6 72,400 21.2 70,600 20.7
Sensible 73,600 21.6 72,400 21.2 70,600 20.7
85°F DB, 64.4°F WB (29.4°C DB, 18
°
C WB) 32% RH
Total 69,700 20.4 68,400 20.0 66,800 19.6
Sensible 69,700 20.4 68,400 20.0 66,800 19.6
80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH
Total 66,000 19.3 64,400 18.9 63,100 18.5
Sensible 66,000 19.3 64,400 18.9 63,100 18.5
80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH
Total 66,900 19.6 65,300 19.1 63,800 18.7
Sensible 54,600 16.0 54,000 15.8 53,400 15.6
75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH
Total 62,700 18.4 60,800 17.8 59,600 17.5
Sensible 53,000 15.5 52,300 15.3 51,800 15.2
75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH
Total 61,200 17.9 60,700 17.8 59,600 17.5
Sensible 57,000 16.7 60,700 17.8 59,600 17.5
72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH
Total 60,200 17.6 58,200 17.1 57,200 16.8
Sensible 52,000 15.2 51,200 15.0 50,700 14.9
72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH
Total 58,900 17.3 58,400 17.1 57,500 16.8
Sensible 55,800 16.3 58,400 17.1 57,500 16.8
Fan Data (Blower A12x9AT)**
Standard Air, CFM (CMH) 2800 (4760) 2800 (4760) 2800 (4760)
Standard Fan Motor, hp (kW) 1-1/2 (1.1) 1-1/2 (1.1) 1-1/2 (1.1)
Opt Fan Motor, hp (kW) 2 (1.5) 2 (1.5) 2 (1.5)
Ext Static, in. WG (Pa) .3 (75) .3 (75) .3 (75)
Evaporator Coil (V-FRAME, at standard conditions)
Face Area, ft.
2
(m
2
) 6.67 (.62) 6.67 (.62) 6.67 (.62)
Rows 4 4 4
Face Velocity - FPM (m/s) 405 (2.1) 405 (2.1) 405 (2.1)
Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard
Capacity, inc. motor heat, BTU/H (
element kW) 56,200 (15) 56,200 (15) 56,200 (15)
Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes std air volume and opt fan motor hp)
Capacity, inc. motor heat, BTU/H (kW) 88,700 (26.0) 88,700 (26.0) 88,700 (26.0)
Flow Rate - GPM (l/s) 5.0 (.32) 5.0 (.32) 5.0 (.32)
Pressure drop - ft. (kPa) 16.9 (50.4) 16.9 (50.4) 16.9 (50.4)
* The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the
standard rating for ASHRAE 127-2001. All capacities are nominal values; actual performance will be ±5%.
** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for
recommendations.