System Data
37
Table 15 Liebert Challenger ITR chilled water data, 50 Hz
Capacity Data kW (BTU/H) @ 7.2°C (45°F ) EWT, 5.6°C (10°F) Water Rise; Net Capacity Data
Indoor Unit
BR = Horizontal Flow
BR 101C
Indoor Unit
BR 101C
37.8ºC DB, 21.1ºC WB (100ºF DB, 70ºF WB) 20% RH, 6.7°C (12°F)
Water Rise
Fan Data (Blower A12x9AT)**
Total kW (BTU/H) 34.0 116,000 Standard Air, CMH (CFM) 4420 (2600)
Sensible kW (BTU/H) 31.9 109,000 Standard Fan Motor, kW (hp) 1.1 (1-1/2)
Flow Rate l/s (GPM) 1.3 19.9 Opt Fan Motor, kW (hp) 1.5 (2)
Pressure Drop kPa (ft) 66.5 22.3 Ext Static, Pa (in. WG) 75 (.3)
35ºC DB, 20.2ºC WB (95ºF DB, 68.3ºF WB) 24% RH,
6.1°C (11°F) Water Rise
Chilled Water Coil (V-Frame, at standard conditions)
Total kW (BTU/H) 31.1 106,000 Face Area, m
2
(ft
2
) .62 (6.67)
Sensible kW (BTU/H) 29.0 99,100 Rows 4
Flow Rate l/s (GPM) 1.3 19.9 Face Velocity, m/s (FPM) 1.9 (375)
Pressure Drop kPa (ft) 66.5 22.3 Electric Reheat 2-Stage (Stainless Steel, Fin Tubular) - Std
32.2ºC DB, 19.2ºC WB (90ºF DB, 66.5ºF WB) 28% RH Capacity, element kW (inc. motor heat, BTU/H) 15 (56,200)
Total kW (BTU/H) 28.2 96,100
Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C (75°F) EAT -
Optional (Includes std air volume and opt. fan motor hp)
Sensible kW (BTU/H) 26.0 88,900
Flow Rate l/s (GPM) 1.3 20.0 Capacity, inc. motor heat, kW (BTU/H) 25.3 (86,200)
Pressure Drop kPa (ft) 66.8 22.4 Flow Rate, l/s (GPM) .32 (5.0)
29.4ºC DB, 18ºC WB (85ºF DB, 64.4ºF WB) 32% RH Pressure drop, kPa (ft.) 50.4 (16.9)
Total kW (BTU/H) 24.7 84,200 Infrared Humidifier - Standard
Sensible kW (BTU/H) 23.0 78,400 Capacity, kg/hr (lb/hr) 5 (11)
Flow Rate l/s (GPM) 1.1 17.6 kW 4.8
Pressure Drop kPa (ft) 52.7 17.7 Steam Generating Humidifier - Optional
26.7ºC DB, 17.1ºC WB (80ºF DB, 62.7ºF WB) 38% RH Capacity, kg/hr (lb/hr) 5 (11)
Total kW (BTU/H) 21.5 73,500 kW 3.9
Sensible kW (BTU/H) 19.6 66,900
Filter Section - Efficiencies per ASHRAE 52.1 - Disposable
Type
Flow Rate l/s (GPM) 1.0 15.8
20% Eff. available in 51mm (2") - Standard, or Optional 102mm (4")
Depths; other Optional 102mm (4") Eff. are: 30%, 40-45%, 60-65%
Pressure Drop kPa (ft) 42.9 14.4 Nominal Size - mm 28.5 x 29.5
26.7ºC DB, 19.2ºC WB (80ºF DB, 66.5ºF WB) 50% RH Nominal Size - inches 724 x 749
Total kW (BTU/H) 27.5 94,000 Effective Surface Area - m
2
(ft
2
) 2.2 (24.1)
Sensible kW (BTU/H) 19.8 67,500 Connection Sizes-Challenger ITR Unit
Flow Rate l/s (GPM) 1.2 19.7 CW Supply 1 1/8 OD Cu
Pressure Drop kPa (ft) 65.9 22.1 CW Return 1 1/8 OD Cu
23.9ºC DB, 16.9ºC WB (75ºF DB, 62.5ºF WB) 50% RH Humidifier Supply 1/4 OD Cu
Total kW (BTU/H) 20.4 69,700 Condensate Drain 1/2 FPT
Sensible kW (BTU/H) 16.8 57,500 Control Valve
Flow Rate l/s (GPM) 0.9 14.7 Maximum design water pressure 1034.4 kPa (150 PSI)
Pressure Drop kPa (ft) 38.1 12.8 Valve Actuator Modulating
23.9ºC DB, 16.2ºC WB (75ºF DB, 61.1ºF WB) 45% RH Sensors Proportional
Total kW (BTU/H) 19.0 64,800 Valve Body Three-Way
Sensible kW (BTU/H) 17.4 59,500 Valve Size, in. 1
Flow Rate l/s (GPM) 0.8 13.3 Cv 13.9
Pressure Drop kPa (ft) 31.6 10.6 Two-Way Valve (Optional)
22.2ºC DB, 15.6ºC WB (72ºF DB, 60.1ºF WB) 50% RH Close Off Pressure - kPa (PSI) 483 (70)
Total kW (BTU/H) 16.7 57,100
* The net capacity data has fan motor heat factored in for all ratings
and the entering air condition of 72°F (22.2°C) and 50% RH is the
standard rating for ASHRAE 127-2001.All capacities are nominal
values; actual performance will be ±5%.
** Data rated with 2" 20% ASHRAE filter. Some options or
combinations of options may result in reduced airflow. Consult
factory for recommendations.
Sensible kW (BTU/H) 15.1 51,400
Flow Rate l/s (GPM) 0.8 12.0
Pressure Drop kPa (ft) 26.2 8.8
22.2ºC DB, 14.8ºC WB (72ºF DB, 58.7ºF WB) 45% RH
Total kW (BTU/H) 15.7 53,500
Sensible kW (BTU/H) 15.4 52,400
Flow Rate l/s (GPM) 0.7 11.1
Pressure Drop kPa (ft) 22.6 7.6