Emerson ITR Network Card User Manual


 
Electrical Data
48
Table 27 Liebert Challenger ITR electrical data—50 Hz
Model Type
Self-Contained Split System Evaporator or Chilled Water
B*065A, 070WG, 058G B*059E, 101C
3 Phase, 50Hz
Voltage 200 230 380/415 200 230 380/415
With Electric Reheat and Humidifier (Infrared or Steam Generating) (Note: See Table 28 for units w/SCR reheats.
1
)
Motor 1.1 kW (1.5 hp) 1.1 kW (1.5 hp)
FLA 66.0 64.4 34.4 58.1 54.8 30.8
Motor 1.5 kW (2.0 hp) 1.5 kW (2.0 hp)
FLA 67.7 65.9 35.2 59.8 56.3 31.6
Motor 2.2 kW (3.0 hp) 2.2 kW (3.0 hp)
FLA 70.8 68.6 36.8 62.9 59.0 33.2
Humidifier Only (Infrared or Steam Generating)
Motor 1.1 kW (1.5 hp) 1.1 kW (1.5 hp)
FLA 38.8 36.4 19.1 18.1 15.7 9.1
Motor 1.5 kW (2.0 hp) 1.5 kW (2.0 hp)
FLA 40.5 37.9 19.9 19.8 17.2 9.9
Motor 2.2 kW (3.0 hp) 2.2 kW (3.0 hp)
FLA 43.6 40.6 21.5 22.9 19.9 11.5
Electric Reheat Only (Note: See Table 28 for units w/SCR reheats.
1
)
Motor 1.1 kW (1.5 hp) 1.1 kW (1.5 hp)
FLA 66.0 64.4 34.4 45.3 43.7 24.4
Motor 1.5 kW (2.0 hp) 1.5 kW (2.0 hp)
FLA 67.7 65.9 35.2 47.0 45.2 25.2
Motor 2.2 kW (3.0 hp) 2.2 kW (3.0 hp)
FLA 70.8 68.6 36.8 50.1 47.9 26.8
Without Electric Reheat and Humidifier
Motor 1.1 kW (1.5 hp) 1.1 kW (1.5 hp)
FLA 26.0 25.3 12.7 5.3 4.6 2.7
Motor 1.5 kW (2.0 hp) 1.5 kW (2.0 hp)
FLA 27.7 26.8 13.5 7.0 6.1 3.5
Motor 2.2 kW (3.0 hp) 2.2 kW (3.0 hp)
FLA 30.8 29.5 15.1 10.1 8.8 5.1
1. For Split System Evaporators with SCR reheat, use the values above.
FLA = Full Load Amps (Input Amps)
RLA = Rated Load Amps
LRA = Locked Rotor Amps
* R = In The Row; M = In The Row with Econ-O-Coil