Dimensional Drawings
41
Figure 15 Cabinet and floor planning dimensional data—Split System—Propeller fan condensing unit
A
B
C
Fan Rotation
CCW
(left side)
SL-11081
Pg 4
Left Air
Intake
Shaded area indicates
a minimum clearance of
18" (457mm) for proper air flow
Removable (front) panel for
access to high voltage and low voltage
connections and to refrigeration components
Shaded area indicates
a recommended clearance of
24" (610mm) for for component
access and removal
Shaded area indicates
a minimum clearance of
18" (457mm) for proper air flow
Right Air
Discharge
Removable (Right ) panel
for access to refrigeration component
C
C
C
C
C
Outdoor Propeller Fan Condensing Unit
Model Width (A) Depth (C) Height (B)
Net Weight
lbs (kg)60 Hz 50 Hz Dimensions - Inches (mm)
PFH067A-_L PFH066A-_L 53 (1343) 18 (457) 36-1/4 (918) 351 (159)