Emerson ITR Network Card User Manual


 
Dimensional Drawings
42
Figure 16 Cabinet and floor planning dimensional data—Propeller fan condensing modules—Vertical air
discharge
Figure 17 Cabinet and floor planning dimensional data—Self-contained system—Air-cooled condenser or
drycooler
Shaded area indicates
a recommended clearance
of 24" (610mm) for component
access.
Shaded area indicates
a recommended clearance
of 18" (457mm) for proper
air flow.
Shaded area indicates
a recommended clearance
of 18" (457mm) for proper
air flow.
Top Ai r
Discharge
Right
Air
Intake
Removable front panel for
access to high voltage and
low voltage connections,
and refrigeration components.
Left Air
Intake
Guard
Height
DPN000131
Rev. 0
D
B
Footprint Dimensions
36-1/8"
(918mm)
4-23/32"
(120mm)
25-3/32 "
(637mm)
46-7/32 "
(1174mm)
4" Typ.
(102mm)
53-3/16"
(1351mm)
1/2" Bolt-Down
Holes (6 places)
32-1/8"
(816mm)
2" Typ.
(51mm)
2"
(51mm)
2"
(51mm)
2"
(51mm)
A
C
Model Numbers Dimensional Data in. (mm) Module Weight
60 HZ 50 HZ A B C D lbs (kg) net.
PFH067A-_H PFH066A-_H 53
(1343)
36-1/4
(918)
38-1/2
(978)
5-1/2
(140)
488
(222)
PFHZ67A-_H PFHZ66A-_L
Liebert Lee-Temp Receiver
L = 40" (1016mm)
W = 7-1/2" (190mm)