Emerson ITR Network Card User Manual


 
Electrical Data
56
Alarms
The microprocessor shall activate an audible and visual alarm in event of any of the following condi-
tions:
High Temperature
Low Temperature
High Humidity
Low Humidity
Short Cycle
Compressor Overload (Optional)
Main Fan Overload (Optional)
Humidifier Problem
High Head Pressure
Change Filter
Loss of Air Flow
Low Suction Pressure
Loss of Power
Custom Alarm (#1 to #4)
Custom alarms are four customer accessible alarm inputs to be indicated on the front panel. Custom
alarms can be identified with prepared (programmed) alarm labels for the following frequently used
inputs:
Water Under Floor
Smoke Detected
Standby GC Pump On
Loss of Water Flow
•Standby Unit On
User-customized text can be entered for all four custom alarms. Each alarm (unit and custom) can be
separately enabled or disabled, selected to activate the common alarm, and programmed for a time
delay of 0 to 255 seconds.
Audible Alarm
The audible alarm shall annunciate any alarm that is enabled by the operator.
Common Alarm
A programmable common alarm shall be provided to interface user selected alarms with a remote
alarm device.
Remote Monitoring
All alarms shall be communicated to the Liebert site monitoring system with the following informa-
tion: date and time of occurrence, unit number, and present temperature and humidity.
Analog Inputs
The system shall include four customer accessible analog inputs for sensors provided by others. The
analog inputs shall accept a 4 to 20 mA signal. The user shall be able to change the input to 0 to 5
VDC or 0 to 10 VDC if desired. The gains for each analog input shall be programmable from the front
panel. The analog inputs shall be able to be monitored from the front panel.
Diagnostics
The control system and electronic circuitry shall be provided with self-diagnostics to aid in trouble-
shooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs
shall be indicated as on or off at the front monitor panel.
Control outputs shall be able to be turned on or off from the front monitor panel without using jump-
ers or a service terminal. Each control output shall be indicated by an LED on a circuit board.