Emerson ITR Network Card User Manual


 
System Data
26
Table 4 Liebert Challenger ITR air-cooled data—50 Hz
System Type
BR = Horizontal Flow
Self-Contained
Split Systems
w/Outdoor Prop-Fan
Condensing Unit
w/Indoor Centrifugal
Condensing Unit
Indoor Unit BR 065A BR 059E BR 059E
Net Capacity Data
kW BTU/H kW BTU/H kW BTU/H
37.8°C DB, 21.1°C WB (100°F DB, 70°F WB) 20% RH
Total 22.4 76,300 25.8 87,900 21.0 71,800
Sensible 22.4 76,300 25.8 87,900 21.0 71,800
Non Standard Flow Rates 2300 CFM 2100 CFM
35°C DB, 20.2°C WB (95°F DB, 68.3°F WB) 24% RH
Total 22.0 75,100 24.3 83,100 21.3 72,600
Sensible 22.0 75,100 24.3 83,100 21.3 72,600
32.2°C DB, 19.2°C WB (90°F DB, 66.5°F WB) 28% RH
Total 20.9 71,200 23.0 78,400 20.2 68,800
Sensible 20.9 71,200 23.0 78,400 20.2 68,800
29.4°C DB, 18°C WB (85°F DB, 64.4°F WB) 32% RH
Total 19.7 67,200 21.6 73,800 19.1 65,100
Sensible 19.7 67,200 21.6 73,800 19.1 65,100
26.7°C DB, 17.1°C WB (80°F DB, 62.7°F WB) 38% RH
Total 18.6 63,600 20.3 69,300 18.0 61,400
Sensible 18.6 63,600 20.3 69,300 18.0 61,400
26.7°C DB, 19.2°C WB (80°F DB, 66.5°F WB) 50% RH
Total 19.0 64,900 21.3 72,600 18.3 62,400
Sensible 15.2 51,800 16.0 54,700 14.9 50,900
23.9°C DB, 16.9°C WB (75°F DB, 62.5°F WB) 50% RH
Total 17.8 60,600 19.5 66,600 17.0 58,100
Sensible 14.7 50,300 15.5 52,800 14.4 49,300
23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB) 45% RH
Total 17.3 59,100 19.0 64,700 16.6 56,700
Sensible 15.8 54,000 16.5 56,300 15.5 53,000
22.2°C DB, 15.6°C WB (72°F DB, 60.1°F WB) 50% RH
Total 17.0 58,100 18.6 63,600 16.3 55,700
Sensible 14.4 49,300 15.1 51,700 14.2 48,300
22.2°C DB, 14.8°C WB (72°F DB, 58.7°F WB) 45% RH
Total 16.7 56,900 18.0 61,500 16.3 55,700
Sensible 15.5 52,900 16.1 54,900 16.3 55,700
Fan Data (Blower A12x9AT)**
Standard Air, CMH (CFM) 4420 (2600) 4420 (2600) 4420 (2600)
Standard Fan Motor, kW (hp) 1.1 (1-1/2) 1.1 (1-1/2) 1.1 (1-1/2)
Opt Fan Motor, kW (hp) 1.5 (2) 1.5 (2) 1.5 (2)
Ext Static, Pa (in. WG) 75 (.3) 75 (.3) 75 (.3)
Evaporator Coil (V-Frame, at Standard Conditions)
Face Area, m
2
(ft.
2
) .62 (6.67) .62 (6.67) .62 (6.67)
Rows 4 4 4
Face Velocity, m/s (FPM) 1.9 (375) 1.9 (375) 1.9 (375)
Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard
Capacity, element kW (inc. motor heat, BTU/H) 15 (56,200) 15 (56,200) 15 (56,200)
Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C (75°F) EAT - Opt. (inc. standard air volume and optional fan motor hp)
Capacity, inc. motor heat, kW (BTU/H) 25.3 (86,200) 25.3 (86,200) 25.3 (86,200)
Flow Rate, l/s (GPM) .32 (5.0) .32 (5.0) .32 (5.0)
Pressure drop, kPa (ft.) 50.4 (16.9) 50.4 (16.9) 50.4 (16.9)
* The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the
standard rating for ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%.
** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for
recommendations.